Specifications
Range of product | PowerLogic P5 |
---|---|
Product or component type | Protection and control relay |
Relay application | Universal |
product reference | P5U20-AABB-BAAAH-AEAD |
Mounting case size | 20TE |
Device mounting | Flush |
Mounting support | Rack |
Mounting mode | Withdrawable |
power supply | 100…230 V AC 24…250 V DC |
measuring inputs | : 1/5 A CT phase current 3 : 1/5 A CT residual current 1 : 1 A CT current 1 : VT voltage 4 : digital 10 |
number of Digital Inputs (DI) | 10 |
number of analogue inputs | 0 |
number of Digital Outputs (DO) | 1 watchdog 7 digital |
number of analogue outputs | 0 |
communication ports | USB port 2 front Extension port 1 rear with backup memory |
communication protocols | IEC 61850 ed. 1 IEC 61850 ed. 2 IEC 60870-5-101 DNP3 TCP Modbus TCP EtherNet/IP |
Redundancy communication port protocol | RSTP PRP |
Cybersecurity | Password protection Port hardening Firmware signature Client IP address filter Secured communication with assciated tools |
protection functions | Phase overcurrent 50/51 Earth fault overcurrent 50N/51N Broken conductor 46 I2/I1 Cold load pick-up 67N Switch ON to fault (SOTF) 67NI H2 detection 68H2 H5 detection 68H5 Breaker failure 50BF Recloser 79 Thermal overload protection 49 Phase undercurrent 37 Excessive starting time, locked rotor 48/51LR Motor restart inhibition 66 Capacitor overvoltage 59C Negative sequence overcurrent 46 Capacitor bank unbalance 51C Restricted earth fault 64REF Lockout relay 86 CT supervision 60 Programmable stages 99 Programmable curve 27P Programmable logic 59N Underfrequency 81/81N Rate of change of frequency 81R Synchro-check 25 VT supervision 60 Negative sequence overcurrent 47 Programmable curve |
Arc flash protection | No |
measurement functions | Current 3-phase Current zero sequence Current positive sequence Current negative sequence Current ratio of negative and positive Frequency phase to earth Current phasor diagram view Current 2nd, 15th harmonics with THD Voltage positive sequence Voltage negative sequence Voltage ratio of negative and positive Short circuit fault reactance Fault location current Earth fault reactance Frequency Active power RMS active power Reactive power RMS reactive power Apparent power RMS apparent power Active energy Reactive energy Cos φ Tan φ Power angle Power factor Voltage phasor diagram view Voltage 2nd, 15th harmonics with THD Voltage interruption Condition monitoring CB wear |
control functions | Switchgear control and monitoring Programmable switchgear interlocking Local/remote control on single-line diagram 2 function keys with I/O keys Local/remote control 2 function keys Mobile application with Easergy SmartApp Web-server Programmable logic |
controllable switchgear devices | 6 controlled + 2 monitored objects |
number of setting groups | 4 |
monitoring functions | Trip circuit supervision 74 Circuit breaker monitoring Relay self-monitoring |
logs and records | Event recording Disturbance recording Tripping context Relay maintenance |
Switchgear diagnosis type | CT/VT supervision ANSI code: 60 CT supervision Trip circuit supervision ANSI code: TCS |
Connections – terminals | Pin removable (digital input/output) Ring lugs removable (current transformer) Pin removable (voltage transformer) Ring lugs (voltage transformer) Screw (connector) |
Operating threshold | 24…230 V AC/DC |
---|---|
Time synchronisation protocol | SNTP |
Software name | EcoStruxure Power Device: virtual simulation test ESetup Easergy Pro |
Web server | Embedded HTTP server |
Display type | LCD 192 x 96 pixels with single line diagram |
Number of key | 1 customizable |
Local signalling | 6 x LED tri-colour programmable 4 x LED red programmable |
Standards | IEC |
Height | 176 mm |
Width | 102 mm |
Depth | 219 mm |
Net weight | 2.5 kg maximum |
Reviews