Specifications
Range of product | PowerLogic P5 |
---|---|
Product or component type | Protection and control relay |
Relay application | Feeder – directional over current |
product reference | P5F30-DDCD-GABEH-AEAC |
Mounting case size | 30TE |
Device mounting | Flush |
Mounting support | Rack |
Mounting mode | Withdrawable |
power supply | 100…230 V AC 48…250 V DC |
measuring inputs | : 1/5 A CT phase current 3 : 1/5 A CT residual current 1 : 1 A CT current 1 : voltage 4 |
number of Digital Inputs (DI) | 19 |
number of analogue inputs | 0 |
number of Digital Outputs (DO) | 1 watchdog 18 digital |
number of analogue outputs | 0 |
communication ports | USB port 2 front Extension port 1 rear with backup memory RJ45 4 rear |
communication protocols | IEC 61850 ed. 1 IEC 61850 ed. 2 DNP3 over ethernet Modbus TCP Modbus RTU IEC 60870-5-101 IEC 60870-5-103 EtherNet/IP DNP3 RTU |
Redundancy communication port protocol | RSTP |
Cybersecurity | Password protection Port hardening Firmware signature Client IP address filter Secured communication with assciated tools |
protection functions | Phase overcurrent 50/51 Directional phase overcurrent 67 Earth fault overcurrent 50N/51N Directional earth fault 67N Transient earth fault 67NI Neutral admittance 21YN Broken conductor 46 I2/I1 Cold load pick-up Switch ON to fault (SOTF) Breaker failure 50BF Directional active underpower 37P Phase undercurrent 37 Excessive starting time, locked rotor 48/51LR Motor restart inhibition 66 Negative sequence overcurrent 46 Overvoltage 59 Undervoltage 27 Positive sequence undervoltage 27P Earth fault overvoltage 59N Underfrequency 81/81N Overfrequency 81/81N Restricted earth fault 64REF Lockout relay 86 CT supervision 60 VT supervision 60 H2 detection 68H2 H5 detection 68H5 Earth fault wattmetric 32N Programmable stages 99 Programmable curve Programmable logic Current unbalance 46 I2/I1 |
Arc flash protection | No |
measurement functions | Current 3-phase Current zero sequence Current positive sequence Current negative sequence Current ratio of negative and positive Voltage zero sequence Voltage positive sequence Voltage negative sequence Voltage 3-phase Voltage residual Frequency Voltage phasor diagram view Current phasor diagram view Current 2nd, 15th harmonics with THD |
control functions | Switchgear control and monitoring Programmable switchgear interlocking Local/remote control 2 function keys Programmable logic |
controllable switchgear devices | 6 controlled + 2 monitored objects |
number of setting groups | 4 |
monitoring functions | Trip circuit supervision 74 Circuit breaker monitoring Relay self-monitoring |
logs and records | Event recording Disturbance recording Tripping context Relay maintenance |
Connections – terminals | Pin removable (digital input/output) Ring lugs removable (current transformer) Pin removable (voltage transformer) Ring lugs (voltage transformer) Screw (connector) |
Time synchronisation protocol | SNTP |
---|---|
Software name | EcoStruxure Power Device: virtual simulation test ESetup Easergy Pro |
Web server | Embedded HTTP server |
Display type | Colour LCD 480 x 272 pixels |
Number of key | 7 customizable |
Local signalling | 10 x LED tri-colour programmable 4 x LED red programmable |
Height | 176 mm |
Width | 152 mm |
Depth | 219 mm |
Net weight | 3.5 kg maximum |