Specifications

 

Main
Relay application Motor
Range of product Sepam series 40
Device short name M41
Control and monitoring type Latching/acknowledgement ANSI code: 86
Logic discrimination ANSI code: 68 (option)
Switching of groups of settings
Annunciation ANSI code: 30
Circuit breaker/contactor control ANSI code: 94/69
Logic equation editor 100 operators
Metering type Phase current I1, I2, I3 RMS, residual current I0
Demand current I1, I2, I3, peak demand current IM1, IM2, IM3
Temperature (option)
Voltage U21, U32, U13, V1, V2, V3, residual voltage V0
Frequency
Positive sequence voltage Vd/rotation direction-negative sequence voltage Vi
Active, reactive, apparent power P,Q,S-peak demand power PM, QM, power factor
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) (option)
Network and machine diagnosis type Unbalance ratio/negative sequence current Ii
Disturbance recording
Thermal capacity used
Remaining operating time before overload tripping
Waiting time after overload tripping
Running hours counter/operating time
Starting current and time
Start inhibit time, number of starts before inhibition
Tripping context
Phase displacement
Switchgear diagnosis type Cumulative breaking current
Trip circuit supervision (option)
Number of operations, operating time charging time (option)
CT/VT supervision ANSI code: 60FL
Complementary
Type of measurement Voltage
Current
Peak demand power
Energy
Power (P,Q)
Frequency
Power factor
Temperature
Protection type Thermal overload protection ANSI code: 49RMS (2)
Phase undercurrent ANSI code: 37 (1)
Excessive starting time, locked rotor ANSI code: 48/51LR/14 (1)
Starts per hour ANSI code: 66 (1)
Neutral voltage displacement ANSI code: 59N (2)
Breaker failure ANSI code: 50BF (1)
Undervoltage protection ANSI code: 27/27S (2)
Overvoltage protection ANSI code: 59 (2)
Directional earth fault ANSI code: 67N/67NC (2)
Temperature monitoring (8 or 16 RTDs) ANSI code: 38/49T (option)
Positive sequence undervoltage ANSI code: 27D (2)
Directional reactive overpower ANSI code: 32Q/40 (1)
Phase overcurrent ANSI code: 50/51 (4)
Earth fault/sensitive earth fault ANSI code: 50N/51N (4)
Earth fault/sensitive earth fault ANSI code: 50G/51G (4)
Remanent undervoltage ANSI code: 27R (1)
Negative sequence/unbalance ANSI code: 46 (2)
Negative sequence overvoltage ANSI code: 47 (1)
Overfrequency ANSI code: 81H (2)
Underfrequency ANSI code: 81L (4)
Directional active overpower ANSI code: 32P (1)
Communication port protocol Measurement readout ( option ) : Modbus
Remote indication and time tagging of events ( option ) : Modbus
Remote control orders ( option ) : Modbus
Remote protection setting ( option ) : Modbus
Transfer of disturbance recording data ( option ) : Modbus
Input output max capacity 10 inputs + 8 outputs
Communication compatibility Modbus TCPIP
IEC 61850
Modbus RTU
DNP3
IEC 60870-5-103
User machine interface type Without
Advanced
Remote