Specifications

 

Main
Using the relay Substation
Product range Sepam series 40
Device Name S40
type of control and monitoring Acknowledgement/lock ANSI code: 86
Logic selectivity ANSI code: 68 (option)
Switching of groups of settings
Warning ANSI code: 30
Contactor/circuit breaker control ANSI code: 94/69
Logic equation editor 100 operators
type of counting Phase current I1, I2, I3 RMS, residual current I0
Demand current I1, I2, I3, peak demand current IM1, IM2, IM3
Voltage U21, U32, U13, V1, V2, V3, residual voltage V0
Frequency
Positive sequence voltage Vd/ rotation direction-negative sequence voltage Vi
Active, reactive, apparent power P,Q,S-peak demand power PM, QM, power factor
Calculated active and reactive energy (+/- Wh, +/- VAR.h)
Active and reactive energy by pulse counting (+/- Wh, +/- VAR.h) (option)
network and machine diagnostic type Unbalance rate/negative sequence current Ii
Recording of oscilloscope disturbances
Triggering context
Phase displacement
Type of diagnostic cut-off organ Cumulative breaking current
Trip circuit supervision (option)
Number of operations, operating time charging time (option)
TC/TP supervision ANSI code: 60FL
Complementary
Type of measurement Power (P,Q)
Frequency
Current
Power factor
Voltage
Peak demand
power Energy
type of protection Recloser (4 cycles) ANSI code: 79 (option)
Neutral voltage displacement ANSI code: 59N (2)
Circuit breaker failure ANSI code: 50BF (1)
Undervoltage protection ANSI code: 27/27S (2)
Overvoltage protection ANSI code: 59 (2)
Phase overcurrent ANSI code: 50/51 (4)
Earth fault/sensitive earth fault ANSI code: 50N/51N (4)
Earth fault/sensitive earth fault ANSI code: 50G/51G (4)
Negative sequence/unbalance ANSI code: 46 (2)
Negative sequence overvoltage ANSI code: 47 (1)
Overfrequency ANSI code: 81H (2)
Underfrequency ANSI code: 81L (4)
communication protocol Reading of measurements (option): Modbus
Remote indication and fixing of event time (option): Modbus
Remote commands (option): Modbus
Remote protection setting (option): Modbus
Transfer of disturbance recording data (option): Modbus
max. input/output capacity 10 inputs + 8 outputs
Communication Compatibility Modbus RTU
IEC 60870-5-103
DNP3
TCPIP Modbus
IEC 61850
user machine interface type Evolved