Specifications
Relay application | Generator |
---|---|
Range of product | Sepam series 40 |
Device short name | G40 |
Control and monitoring type | Latching/acknowledgement ANSI code: 86 Logic discrimination ANSI code: 68 (option) Switching of groups of settings Annunciation ANSI code: 30 Circuit breaker/contactor control ANSI code: 94/69 Logic equation editor 100 operators |
Metering type | Phase current I1, I2, I3 RMS, residual current I0 Demand current I1, I2, I3, peak demand current IM1, IM2, IM3 Temperature (option) Voltage U21, U32, U13, V1, V2, V3, residual voltage V0 Frequency Positive sequence voltage Vd/rotation direction-negative sequence voltage Vi Active, reactive, apparent power P,Q,S-peak demand power PM, QM, power factor Calculated active and reactive energy (+/- W.h, +/- VAR.h) Active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) (option) |
Network and machine diagnosis type | Unbalance ratio/negative sequence current Ii Disturbance recording Thermal capacity used Remaining operating time before overload tripping Waiting time after overload tripping Running hours counter/operating time Tripping context Phase displacement |
Switchgear diagnosis type | Cumulative breaking current Trip circuit supervision (option) Number of operations, operating time charging time (option) CT/VT supervision ANSI code: 60FL |
Type of measurement | Peak demand power Power (P,Q) Current Temperature Frequency Energy Power factor Voltage |
---|---|
Protection type | Thermal overload protection ANSI code: 49RMS (2) Neutral voltage displacement ANSI code: 59N (2) Breaker failure ANSI code: 50BF (1) Undervoltage protection ANSI code: 27/27S (2) Overvoltage protection ANSI code: 59 (2) Temperature monitoring (8 or 16 RTDs) ANSI code: 38/49T (option) Directional reactive overpower ANSI code: 32Q/40 (1) Phase overcurrent ANSI code: 50/51 (4) Earth fault/sensitive earth fault ANSI code: 50N/51N (4) Earth fault/sensitive earth fault ANSI code: 50G/51G (4) Negative sequence/unbalance ANSI code: 46 (2) Negative sequence overvoltage ANSI code: 47 (1) Overfrequency ANSI code: 81H (2) Underfrequency ANSI code: 81L (4) Directional active overpower ANSI code: 32P (1) Voltage-restrained overcurrent ANSI code: 50V/51V (1) |
Communication port protocol | Measurement readout ( option ) : Modbus Remote indication and time tagging of events ( option ) : Modbus Remote control orders ( option ) : Modbus Remote protection setting ( option ) : Modbus Transfer of disturbance recording data ( option ) : Modbus |
Input output max capacity | 10 inputs + 8 outputs |
Communication compatibility | Modbus TCPIP IEC 61850 DNP3 Modbus RTU IEC 60870-5-103 |
User machine interface type | Without Remote Advanced |