Specifications

 

Main
Relay application Generator
Range of product Sepam series 40
Device short name G40
Control and monitoring type Latching/acknowledgement ANSI code: 86
Logic discrimination ANSI code: 68 (option)
Switching of groups of settings
Annunciation ANSI code: 30
Circuit breaker/contactor control ANSI code: 94/69
Logic equation editor 100 operators
Metering type Phase current I1, I2, I3 RMS, residual current I0
Demand current I1, I2, I3, peak demand current IM1, IM2, IM3
Temperature (option)
Voltage U21, U32, U13, V1, V2, V3, residual voltage V0
Frequency
Positive sequence voltage Vd/rotation direction-negative sequence voltage Vi
Active, reactive, apparent power P,Q,S-peak demand power PM, QM, power factor
Calculated active and reactive energy (+/- W.h, +/- VAR.h)
Active and reactive energy by pulse counting (+/- W.h, +/- VAR.h) (option)
Network and machine diagnosis type Unbalance ratio/negative sequence current Ii
Disturbance recording
Thermal capacity used
Remaining operating time before overload tripping
Waiting time after overload tripping
Running hours counter/operating time
Tripping context
Phase displacement
Switchgear diagnosis type Cumulative breaking current
Trip circuit supervision (option)
Number of operations, operating time charging time (option)
CT/VT supervision ANSI code: 60FL
Complementary
Type of measurement Peak demand power
Power (P,Q)
Current
Temperature
Frequency
Energy
Power factor
Voltage
Protection type Thermal overload protection ANSI code: 49RMS (2)
Neutral voltage displacement ANSI code: 59N (2)
Breaker failure ANSI code: 50BF (1)
Undervoltage protection ANSI code: 27/27S (2)
Overvoltage protection ANSI code: 59 (2)
Temperature monitoring (8 or 16 RTDs) ANSI code: 38/49T (option)
Directional reactive overpower ANSI code: 32Q/40 (1)
Phase overcurrent ANSI code: 50/51 (4)
Earth fault/sensitive earth fault ANSI code: 50N/51N (4)
Earth fault/sensitive earth fault ANSI code: 50G/51G (4)
Negative sequence/unbalance ANSI code: 46 (2)
Negative sequence overvoltage ANSI code: 47 (1)
Overfrequency ANSI code: 81H (2)
Underfrequency ANSI code: 81L (4)
Directional active overpower ANSI code: 32P (1)
Voltage-restrained overcurrent ANSI code: 50V/51V (1)
Communication port protocol Measurement readout ( option ) : Modbus
Remote indication and time tagging of events ( option ) : Modbus
Remote control orders ( option ) : Modbus
Remote protection setting ( option ) : Modbus
Transfer of disturbance recording data ( option ) : Modbus
Input output max capacity 10 inputs + 8 outputs
Communication compatibility Modbus TCPIP
IEC 61850
DNP3
Modbus RTU
IEC 60870-5-103
User machine interface type Without
Remote
Advanced