Specifications
| Product range | PowerLogic P5 |
|---|---|
| Type of product or equipment | Protection and relay control |
| Using the relay | Engine |
| Product reference | P5M30-BACB-GABAH-BAEA |
| Circuit breaker type | 30TE |
| Mounting the device | Recessed |
| Installation mode | Detachable |
| Food | 48…250 V DC 100…230 V AC |
| Measuring inputs | : TC 1/5 A PHASE CURRENT 3 : TC 1/5 A residual current 1 : TC 1 A residual current 1 : TP 101 V/110 V voltage 4 |
| Number of sensors | 0 temperature sensor(s) 0 arc flash sensor(s) |
| Number of digital inputs (DI) | 16 |
| number of analogue inputs | 0 |
| Number of digital outputs (DO) | 11 DO 1 guard dog |
| Number of analog outputs | 0 |
| Communication ports | RJ45 2 rear panel Expansion port 1 rear panel with backup memory USB port 2 front panel |
| Communication protocols | IEC 61850 ed. 1 IEC 61850 ed. 2 DNP3 over ethernet Modbus TCP Ethernet IP |
| Communication protocol | RSTP |
| Cybersecurity | Communication port hardening Firmware signature Client IP address filter Secure communication with associated tools Security policy management Role-based access control LDAP security log RADIUS-based user authentication IEC 62443-4-2 SL1 |
| Protective functions | Phase overcurrent 50/51 Directional phase overcurrent 67 Earth overcurrent 50N/51N Restricted earth fault 64REF Directional earth overcurrent 67N Transient intermittent 67NI Neutral admission 21YN Wattmetric earth fault 32N Broken conductor 46 I2/I1 Current unbalance 46 I2/I1 Selective overcurrent logic Fault triggering (SOTF) H2 detection H5 detection Circuit breaker failure 50BF Directional active underpower 37P Phase undercurrent 37 Excessively long start, rotor lock 48/51LR Motor restart inhibition 66 Negative sequence overcurrent 46 Overvoltage 59 Undervoltage 27 Positive sequence undervoltage 27P Residual maximum voltage 59N Underfrequency 81/81N Locking 86 CT supervision 60 VT supervision 60 Programmable thresholds 99 Programmable logic Programmable curve |
| Measuring functions | Three-phase current Zero sequence current Positive component current Negative component current Ratio of reverse to direct current Current and voltage diagram Current 2nd, 15th harmonics with TDH Three-phase voltage Residual voltage Zero sequence voltage Positive component voltage Negative component voltage Frequency |
| Control functions | Circuit breaker control and monitoring Programmable interlock Local/remote control |
| Controllable devices | 6 objects ordered + 2 objects monitored |
| Number of setting groups | 4 |
| Monitoring functions | Trip circuit supervision 74 Circuit breaker supervision Relay self-supervision |
| Records and recordings | Event recording Recording of oscilloscope disturbances Triggering context Relay maintenance |
| Type of diagnostic cut-off organ | TC/TP supervision ANSI code: 60 Trip circuit supervision ANSI code: 74 |
| Connection mode | Screws (logic input/output) Ring terminals (analog inputs and outputs) |
| Synchronization protocol | SNTP |
|---|---|
| Software Name | EcoStruxure Power Device ESetup Easergy Pro: virtual injection test |
| Web Server | Built-in HTTP server |
| Display type | 480 x 272 pixel color LCD |
| Number of keys | 7 customizable |
| Voltage indication | 4 x LED 10 x LED 3 colors programmable |
| height | 176 mm |
| Width | 152 mm |
| Depth | 219 mm |
| Weight | 3.5 kg |


Reviews